Mod. | Vers. | 15 R | 17 R | 110 R | 113 Z | |
Cooling capacity (outdoor temparature 35°C – chilled water temperature12/7°C) | H | kW | 4,71 | 6,1 | 9 | 10,82 |
Power input | H | kW | 1,52 | 1,96 | 2,9 | 3,49 |
Heating capacity (outdoor temperature 7°C 90% R.H. -hot water temp. 45°C) | H | kW | 5,44 | 7,44 | 11,98 | 14,1 |
Total EER 100% | H | kW | 1,7 | 2,32 | 3,7 | 4,35 |
Total COP 100% | H | 3,1 | 3,11 | 3,11 | 3,1 | |
European Seasonal EER | H | 3,2 | 3,21 | 3,22 | 3,24 | |
Number of refrigerant circuits | N. | 1 | 1 | 1 | 1 | |
Number of compressors | N. | 1 | 1 | 1 | 1 | |
Type of compressors | Rotary | Twin Rotary | Scroll | |||
pressure sound level (calculated according to ISO 3744 at 5 mt distance from the unit) | dB(A) | 24 ~ 44 | 26 ~ 45 | 27 ~ 47 | 27 ~ 48 | |
Type of compressors | 49 ~ 69 | 51 ~ 70 | 52 ~ 72 | 52 ~ 73 | ||
Power sound level | kW | 2,89 | 3,88 | 5,65 | 6,35 | |
Maximum power input | A | 12,9 | 17,4 | 25,3 | 15,5 | |
Maximum full load current | A | 8,2 | 10,3 | 16,4 | 9,6 | |
Electrical power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 400/3/50 | ||
Water flow | m3/h | 1,01 | 1,37 | 2,16 | 2,56 | |
External head pressure | kPa | 43 | 32 | 38 | 39 |
- DC INVERTER scroll or rotary compressor.
- Fans propeller type.
- Air side heat exchanger with seamless coppertubes and aluminium fins.
- AISI 316 stainless steel brazewelded platestype with differential pressure switch.
- Hydraulic circuit with expansion vessel, variableflow rate water pump, safety valve andautomatic air release valve.
- Electronic expansion valve.
- Microprocessor.
- Outdoor temperature probe.
- Low ambient condensing pressure control withvariable fan speed modulation.
- Electrical panel with main switch.
- Casing and panels in galvanised and painted steel
VERSIONS:
C Chillers with hydraulic kit.
H Heat pumps with hydraulic kit.
VB Hydraulic versions: Built in water tank, water gauges and connectionkit supplied loose.